ERROR type fault messages
All faults of the ERROR type must be reset manually:
RM10.5T, RMS10.5T, RMS10.5XT: Press the control knob for 2 seconds.
RM10.5S, RMS10.5S, RMS10.5XS: Press for 2 seconds.
✓ A beep sounds.
✓ The error has been reset.
ERROR type | Fault description | Solution |
---|---|---|
E03 | No connection between power module and display | Contact an authorized customer service point. |
E07 | No cooling capacity in gas mode |
Check if the device is at an angle and adjust it so it is level, if necessary. Reset the error. Contact customer service if this error occurs again. |
E08 | No cooling capacity in AC power mode |
Check if the device is at an angle and adjust it so it is level, if necessary. Reset the error. Contact customer service if this error occurs again |
E09 | No cooling capacity in DC power mode |
Check if the device is at an angle and adjust it so it is level, if necessary. Reset the error. Contact customer service if this error occurs again. |
E12 | Gas valve test error Gas operation not possible |
Reset the error. Contact customer service if this error occurs again. |
E13 | Internal communication error Gas operation not possible | Reset the error. Contact customer service if this error occurs again |
E14 | In stand-alone gas mode: The battery charge of the battery packs is too low | Insert new batteries and then reset the error |
E50 | Gas lock after 3 ignition attempts | Ignition not possible. The gas cylinder is empty. Replace the gas cylinder. Reset the error. |
E51 | Gas lock, internal error in the power module |
Reset the error. |
E52 | Ground contact, gas valve Reset the error |
Contact customer service if this error occurs again. |
E53 | Ground contact, ignition electrode |
Reset the error. Contact customer service if this error occurs again |